Prostar 20kVA to 300kVA Modular UPS system

SKU: MPS90K-30U - MPS300K-42U Category:

Mars Series Modular UPS uses high efficient online double conversion technology, and the efficiency can reach 94.5%. And it’s seamless integrated with the latest data room designs, which is a high-reliability redundant scalable modular UPS systems.

Mars Series Modular UPS system with extremely flexible architecture, and it’s power modules using online hot-swappable design, which can easily be removed, installed and maintained when the system is running, but without affecting system operation and output, which made the investment plan comes true according to the requirement. Which could both to meet the user extended equipment needs at later period, but also reduce the initial purchase cost.

Mars Series Modular UPS provides 20KW and 30KW power modules and two kinds of cabinets system, the user can be flexibly configured according to the load demand. The single cabinet can achieve maximum capacity up to 300KW, and provide 2 kinds ups system of 90KW and 120KW, which could be with built-in battery modules, for users choose easily.

Cabinet Model MPS90K-30U MPS120K-42U MPS120K-30U MPS180K-30U MPS210K-42U MPS300K-42U
Maximum Capacity 90KW 120KW 80KW/120KW 120KW/180KW 210KW 300KVA
Phase 3-phase in / 3-phase out
Battery Voltage 240V Default, 192V/240V Selectable
Battery Type Built-in Battery Module External Battery Pack
Power Module Capacity 30KW 20KW/30KW 30KW 30KW
Max. Power Module NO. 3 4 4 6 7+1 10
Max. Battery Module NO. 3 5
Size, D X W X H (mm) 1100X600X1475 1100 X600X2010 1100 X600X1475 1100 X600X2010
Cabinet Net Weight (Kgs) 675 932 333/335 435/438 515/549 618
Input
Input Voltage 3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Range 305~477VAC at 100% Load; 208~304VAC at <70% Load
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99 @ 100% Load, >0.98 @ 50% Load
Harmonic Distortion (THDi) < 3% @ 100% Load
Output
Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Regulation(Steady state) ≦±1%Typical(Balanced Load);≦±2% Typical (Unbalanced Load)
Voltage Regulation(Transient) ≦±5% Typical
Nominal Frequency 50/60Hz
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for 110%,10 min for 120%,1 min for 150%,200ms for >150%
Harmonic Distortion ≦1.5% THD(Linear Load);≦4% THD( Non-linear Load )
Efficiency Up to 94.5%
Battery/Charger
Nominal Voltage +/- 216V (12V x 36Pcs)
Maximum Voltage +/- 240V (12V x 40Pcs)
Minimum Voltage +/- 192V (12V x 32Pcs)
Float Charging Voltage 2.25V/Cell
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current 8A for each power module (User adjustable)
Standards
Safety IEC/EN 60950-1; IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3
Environment
Operation Temperature 0~40°C
Relative Humidity 0~95% Non-condensing
Altitude <1000m for Nominal power
IP Class IP20
Management
Smart RS-232 or USB Windows® 2000/2003/XP/Vista/2008、Windows® 7/8、Linux、Unix、MAC
Optional SNMP Power management from SNMP manager and web browser

Leave a Reply