Mars Series Modular UPS uses high efficient online double conversion technology, and the efficiency can reach 94.5%. And it’s seamless integrated with the latest data room designs, which is a high-reliability redundant scalable modular UPS systems.
Mars Series Modular UPS system with extremely flexible architecture, and it’s power modules using online hot-swappable design, which can easily be removed, installed and maintained when the system is running, but without affecting system operation and output, which made the investment plan comes true according to the requirement. Which could both to meet the user extended equipment needs at later period, but also reduce the initial purchase cost.
Mars Series Modular UPS provides 20KW and 30KW power modules and two kinds of cabinets system, the user can be flexibly configured according to the load demand. The single cabinet can achieve maximum capacity up to 300KW, and provide 2 kinds ups system of 90KW and 120KW, which could be with built-in battery modules, for users choose easily.
Cabinet Model | MPS90K-30U | MPS120K-42U | MPS120K-30U | MPS180K-30U | MPS210K-42U | MPS300K-42U |
Maximum Capacity | 90KW | 120KW | 80KW/120KW | 120KW/180KW | 210KW | 300KVA |
Phase | 3-phase in / 3-phase out | |||||
Battery Voltage | 240V Default, 192V/240V Selectable | |||||
Battery Type | Built-in Battery Module | External Battery Pack | ||||
Power Module Capacity | 30KW | 20KW/30KW | 30KW | 30KW | ||
Max. Power Module NO. | 3 | 4 | 4 | 6 | 7+1 | 10 |
Max. Battery Module NO. | 3 | 5 | – | – | – | – |
Size, D X W X H (mm) | 1100X600X1475 | 1100 X600X2010 | 1100 X600X1475 | 1100 X600X2010 | ||
Cabinet Net Weight (Kgs) | 675 | 932 | 333/335 | 435/438 | 515/549 | 618 |
Input | ||||||
Input Voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | |||||
Voltage Range | 305~477VAC at 100% Load; 208~304VAC at <70% Load | |||||
Nominal Frequency | 50/60Hz(Auto Sensing) | |||||
Frequency Range | 40Hz~70Hz | |||||
Power Factor | >0.99 @ 100% Load, >0.98 @ 50% Load | |||||
Harmonic Distortion (THDi) | < 3% @ 100% Load | |||||
Output | ||||||
Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | |||||
Voltage Regulation(Steady state) | ≦±1%Typical(Balanced Load);≦±2% Typical (Unbalanced Load) | |||||
Voltage Regulation(Transient) | ≦±5% Typical | |||||
Nominal Frequency | 50/60Hz | |||||
Frequency Range(Synchronized) | 46Hz~54Hz or 56Hz~64Hz | |||||
Overload Capability | 1 hour for 110%,10 min for 120%,1 min for 150%,200ms for >150% | |||||
Harmonic Distortion | ≦1.5% THD(Linear Load);≦4% THD( Non-linear Load ) | |||||
Efficiency | Up to 94.5% | |||||
Battery/Charger | ||||||
Nominal Voltage | +/- 216V (12V x 36Pcs) | |||||
Maximum Voltage | +/- 240V (12V x 40Pcs) | |||||
Minimum Voltage | +/- 192V (12V x 32Pcs) | |||||
Float Charging Voltage | 2.25V/Cell | |||||
Boost Charging Voltage | 2.35V/Cell | |||||
Temperature Compensation | Yes | |||||
Maximum Charging Current | 8A for each power module (User adjustable) | |||||
Standards | ||||||
Safety | IEC/EN 60950-1; IEC/EN 62040-1 | |||||
EMC | IEC/EN 62040-2 Category C3 | |||||
Environment | ||||||
Operation Temperature | 0~40°C | |||||
Relative Humidity | 0~95% Non-condensing | |||||
Altitude | <1000m for Nominal power | |||||
IP Class | IP20 | |||||
Management | ||||||
Smart RS-232 or USB | Windows® 2000/2003/XP/Vista/2008、Windows® 7/8、Linux、Unix、MAC | |||||
Optional SNMP | Power management from SNMP manager and web browser |