PHP120K PF1 3 phase commercial pure sine wave 120kva ups power supply

3 Phase Online UPS | 120KVA / 120KW | OUTPUT PF 1 | 3P/3P | 380Vac/400Vac/415Vac | Max. 6 units in parallel

SKU: PHP120K Category:

Prostar PHP120K PF1 3 phase commercial pure sine wave 120kva ups power supply provides battery backup and AC power protection against power disturbances that can damage electronics or destroy data. It’s recommended for critical IT or corporate infrastructure, telecom, LAN/WAN, security and emergency, financial and light industrial applications.

3 phase commercial 120kva ups is specially designed with pluggable power module and front access to simplify maintenance.

PF1 3 phase pure sine wave 120kva ups is non-isolated, redundant, scalable, 3 Phase Online UPS power protection system designed to cost effctively provide high levels of availability.

Voltage and Frequency Independent (VFI) design allows continuous operation at any supported voltage at either 50 or 60 Hz. Zero transfer time to battery mode ensures no disruption to the attached loads. Automatic and Manual Bypass keeps connected equipment powered even during overloads and UPS maintenance.

Prostar High Frequency 3P 3P Online UPS 30KVA 60KVA 100KVA 120KVA 180KVA 200KVA

3 Phase 120KVA UPS Features & Benefits

1. True On-Line Double Conversion 3 Phase

  • Provides fully regulated sine wave AC output for critical telecom, network, security, financial, corporate and light industrial applications
  • +/-1% output voltage regulation in online and battery modes
  • Output power factor 1 is allowing for more connected devices
  • Selectable 380/400/415V output voltage
  • Wide input voltage window (190V–478V) minimizes battery use and prolongs battery life

2. IGBT Inverter Technology

  • Produces output power with less than 2% THD to keep connected equipment functioning at its peak
  • Low <4% THDi input rating and advanced IGBT rectifier

3. Modulity Design

  • Pluggable power module design
  • Front access design for esay maintenance

4. Paralleling Capability

  • Connect up to 6 units in parallel configuration for increased capacity and fault tolerance

5. Automatic and Manual Bypass

  • Manual bypass switch as well as an automatic bypass function ensures 100% availability of connected equipment by safely passing through AC power when the power module requires maintenance

6. ECO Mode

  • Operates at efficiency levels as high as 99% when input line conditions are favorable

7. SNMP/Web Capability

  • Slot for SNMP card network interface or AS400 relay card for remote monitoring and control options

8. Small-Footprint Tower Design

  • Reduced-size black tower case saves valuable floor space
  • Matching external battery cabinets enable extended runtime

Uninterruptible Power Supply Details

Prostar PF1 3 Phase High Frequency Online UPS Front View

Prostar PF1 3 Phase High Frequency Online UPS Front Access Design

UPS Wiring Terminal View

3 Phase PF1 Online UPS 100KW 120KW Rear

Online UPS 100KVA/100KVA Front and Rear View

Terminal Block Wiring Diagram UPS 100KVA 120KVA 180KVA 200KVA

Terminal block wiring

Wiring Parallel System for UPS 100KVA 120KVA 180KVA 200KVA

Wiring Parallel System

The Articles You May Like

Model PHP120K
Capacity 120KVA/120KW
Noise Less than 70 dB @ 1 Meter
Dimension(WxDxH mm) 974x600x1600
Weight(Kgs) 286
INPUT
Nominal Voltage 3 Phases 4 Wires, 380Vac/400Vac/415Vac
Voltage Range 110Vac – 300Vac @50% load; 176-276Vac @100 load
Nominal Frequency 50Hz/60Hz (Automaticly)
Frequency Range 40Hz – 70Hz
Power Factor >=0.99 @100% load
Harmonic Distortion(THDi) < 4% at full liner load
OUTPUT
Voltage 3 Phases 4 Wires, 380Vac/400Vac/415Vac ± 1%
Frequency 50Hz/60Hz±1%
Frequency Range(Synchronized) 46Hz – 54Hz or 56Hz – 64Hz
Harmonic Distortion Linear load<2%, Non-linear load<5%
Overload Capacity 100-110% for 60mins, 111-125% for 10mins, 126-150% for 1 min, >150% for 400ms
Crest Factor 3:1
Wave Form Pure sine wave
Transfer Time 0ms
BYPASS
Nominal Voltage 380Vac/400Vac/415Vac
Voltage Range 305Vac – 457Vac
Frequency Range(Synchronized) 46Hz – 54Hz or 56Hz – 64Hz
Overload Capacity >130% 1 min(default); Continously working until breaker protection(optional)
EFFICIENCY
AC Mode 96.00%
ECO Mode 99.00%
Battery Mode 95.00%
BATTERY
Battery Type Depending on application
Battery Numbers 32 – 40Pcs (Adjustable)
Max. Charging Current 3A – 54A (Adjustable)
Charging Voltage +/- 13.65V*N (N=16 – 20)
INDICATORS
7 Inch Touch LCD Display UPS status, load level, battery level, input/output voltage, discharge time, and fault conditions
SYSTEM
Protection Input over-voltage, under-voltage; output overload, shortcircuit; Inverter over-temperature; Battery under-voltage,over-voltage
IP Protection IP20
Parallel Mode N+1,N+X,can be in parallel with differenct power capacity
ENVIRONMENT
Operating Temperature 0℃ to 40℃
Humidity 0~95% (non-condensing)
Altitude 0 – 1500m at full load
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
MANAGEMENT
Smart RS-232/USB Windows 2000/2003/XP/Vista/7/8,Linux and MAC
SNMP Power managemetn from SNMP manager and web browser