ET30KLV 208v 3 phase dual conversion 30kva hospital ups backup system

208V 3 Phase UPS | 30KVA/24KW | OUTPUT PF 0.8 | 3P/3P | 208V-120V/220V-127V | Max. 8 units in parallel

SKU: ET30KLV Category:

Prostar ET30KLV 208v 3 phase dual conversion 30kva hospital ups backup system can protect patients, staff, and data alike to maintain a hospital’s high efficiency and critical functions running without interruption.

ET LV 208V three-phase uninterruptible power supply delivers top performance for edge, small, and medium data centers, as well as critical infrastructure in commercial and industrial facilities. Its compact design, high-density technology, N+1 redundancy, and fault-tolerant architecture maximize availability, operational efficiency, and critical load protection, while minimizing total cost of ownership.

Facilities install UPS systems to prevent costly downtime and its effects from damaging their business—but without regular testing and maintenance, the backup system may fail when it’s needed most.

ET LV 208V 220V 3 Phase Online UPS

Three phase dual conversion 30kva hospital ups backup system allows you to benefit from a proven design. The robust and easy to operate UPS has excellent overload capability, superior dynamic response and is easy to maintain.

30KVA UPS Features & Benefits

1. Wide input voltage range and frequency range

Designed for harsh electrical environments to save battery life, and suitable for fuel generators or other power generation equipment.

2. Most advanced and high frequency DSP technology

High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology create low input Total Harmonic Distortion (THDi).

3. Super overload capacity

Long-time working under the load of less than 105%; switching to the bypass in 10min under the load of 105% (inclusive) to 125%; switching to the bypass output in 1min under the load of 125% (inclusive) to 150%.

4. Multi-communication Interface

It offers RS232, USB, RS485, CAN, NET, input and output dry contacts, SNMP board, WIFI board, GPRS board and 4G board to monitor the operating status of UPS.

5. Parallel-redundant capable

Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy and share the common battery packs to reduce the cost.

6. ECO

Operating mode that ensures ultra-high efficiency while charging the batteries, conditioning the load power factor, and ensuring a Class 1 output voltage regulation.

7. Cold start and mains start without battery

In the abnormal state of the utility power, the UPS can be started directly with the battery to meet emergency needs.
There is no battery, the UPS can be started directly from the mains power.

8. Lithium-ion batteries compatible

It must be set up separately, not included in the standard configuration.

Hospital UPS System Details

ET uninterruptible power supply UPS 10kva - 30kva front real

ET LV Series 208V Online UPS  Front Panel

ET LV Series 208V UPS  Real

ET uninterruptible power supply UPS communication interface

The Articles You May Like

Model ET30KLV
Capacity 30KVA/24KW
Topology Double conversion online
Noise <65dBA  front side 1M
Dimension(WxDxH mm) 500x800x1300
Weight(Kgs) 325
INPUT
Input Rated Voltage 3P + N + PE, 208Vac/220Vac(L-N: 120Vac/127Vac)
Input Voltage Range 167Vac – 250Vac
Input Rated Frequency 50Hz/60Hz (Auto)
Input Frequency Range 40Hz – 70Hz
Input Power Factor >0.95
Input Current Limit 1.25 times Rated INPUT Current (Settable 0.1 – 1.25)
THDI < 3% full load
BYPASS INPUT
Bypass Input Voltage Range 167Vac – 250Vac
Bypass Input Voltage Regulation Upper Limit: default 20% (Settable 10%/15%/20%/25%)
Lower Limit: default 20% (Settable 10%/20%/30%/40%/50%/60%)
OUTPUT
Output Rated Voltage 3P + N + PE, 208Vac/220Vac ± 1% (L-N: 120Vac/127Vac)
Output Voltage Regulation 0V(Settable ±1V- ±5V)
Output Frequency Mains Mode: tracking BYPASS Input in synchronized state
Battery Mode: 50Hz/60Hz±0.01%
Output Power Factor 0.8
Total Harmonic Distortion (THDU) < 2% at 100% linear load; < 5% at 100% non-linear load
Overload Capacity Supports up to 105% load continuously in double conversion; 105% – 110% load for 60 minutes switching to bypass output; 110% – 125% load for 10 minutes switching to bypass output; 125% – 150% load for 1 minute switching to bypass output; greater than 150% load for 200 milliseconds switching to bypass output
Crest Factor 3:1
Wave Form Pure sine wave
Transfer Time 0ms
ECO MODE
Bypass Output Voltage Regulation Upper Limit: default 5% (Settable 5%/10%/15%)
Lower Limit: default 5% (Settable 5%/10%/15%)
Bypass Output Frequency Regulation Default ±2Hz (Settable ±1Hz/±2Hz/±3Hz)
EFFICIENCY
Efficiency at full load (AC-AC) >93%
Efficiency at ECO Mode >98%
BATTERY
Battery Type Support VRLA Battery, (Lithium-ion Battery Option)
Battery Voltage Default 360Vdc (Settable 336VDC/348VDC/372VDC/384VDC)
Battery Charging Current Charging Rate * Battery Capacity * Group of Battery (Settable for charging rate, battery capacity and group of battery)
SYSTEM
Protection Output short circuit protection, output overload protection, over-temperature protection, low battery voltage protection, output overvoltage / undervoltage protection, fan failure protection
IP Protection IP30
Number of Parallel < 8 Units
Cooling Method Fans
Display 7-inch LCD Touch Screen
Audible Alarm Audible and visible alarms prioritized by severity
ENVIRONMENT
Operating Temperature 0℃ to 40℃ (32F-104F)
Humidity 0~95% (non-condensing)
Altitude < 1000m (Capacity de-rates by 1% for every 100m over 1000m)
Storage Temperature -20℃ to 70℃
COMMUNICATION
Communication Interface Default: RS232/RS485/USB/Dry Contact/EPO (Option: Battery Temperature Compensation)
Communication Slot SNMP/Web interface