Double Conversion UPS | 2000VA / 2000W | 72Vdc | 208V/220V/230V/240V | Without battery inside
Prostar PET1102 single phase pure sine wave double conversion online ups 2kva is a transformer-less UPS that combines high efficiency values with compact footprint and flexible configurations.
The ECO and frequency inverter operation modes highlight the requirements for a modern versatile UPS.
PET1102 single phase online ups 2kva is the perfect solution for supplying sensitive mission critical utilities. The applications require reliability and performance from an uninterruptible power supply.
Single phase pure sine wave double conversion online ups 2kva is a reliable and efficient solution for protecting critical equipment from power disturbances, ensuring uninterrupted operation and minimizing downtime.
UPS Power Supply FAQ
An uninterruptible power supply provides emergency power to a load when the input power source or mains power fails. A UPS system performs three primary functions: conditions the incoming dirty power from the utility company to give you clean, uninterruptible power, provides ride-through power to cover for sags or short-term outages, and enables seamless system shutdown during a complete power outage.
While UPS systems are generally reliable, there can be occasions when they fail. In a worst-case scenario, although it is unlikely, you could lose valuable data which could damage your business and lead to business disruption. This small risk is not worth taking, however, there is a solution.
When you purchase your UPS system, you will receive a manufactures warranty that will cover replacement parts to ensure reliability.
Also, you can protect against possible UPS failures by
You need to make a note of the number of gadgets that need to function in the eventuality of a power cut, and the battery backup power requirement. Additional battery capacity should always be planned keeping future expansion in mind. These pointers will help you choose the right UPS for your ideal backup power supply requirement.
MODEL | PET1102 | |
CAPACITY | 2000VA / 2000W | |
Battery Voltage | 72VDC | |
Size, D X W X H (mm) | 395 X 143 X 222 | |
Net Weight (kgs) | 6 | |
INPUT | ||
Norminal Voltage | 208/220/230/240VAC | |
Input Voltage Range | 110-300VAC | |
Frequency Range | 50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz | |
Phase | Single Phase, L+N+PE | |
Power Factor | ≧ 0.99 @ nominal voltage (input voltage) | |
Harmonic Distortion | ≤4% (Linear Load), ≤5% (Non-linear Load) | |
OUTPUT | ||
Output voltage | 208/220/230/240VAC | |
AC Voltage Regulation | ± 1% (Batt. Mode) | |
Frequency Range(Line Mode) | Synchronized range | |
Frequency Range (Batt. Mode) | 50 Hz or 60Hz ± 0.1% | |
Overload Capacity | AC Mode: Battery Mode: 30mins @102%-110% load 1min @102%-110% load 10mins @110%-130% load 10sec @110%-130% load 30sec @130%-150% load 3sec @110%-130% load 200ms @>150% load 200ms @>150% load |
|
Current Crest Ratio | 3:1 | |
Harmonic Distortion | ≦3% THD (Linear Load);≦5% THD (Non-linear Load) | |
Transfer Time | AC Mode to Battery Mode | 0ms |
Inverter to Bypass | 4ms | |
Waveform (Batt. Mode) | Pure Sine Wave | |
EFFICIENCY | ||
AC Mode | 95.5% | |
Battery Mode | 91.5% | |
BATTERY | ||
Battery Type | Depending on applications | |
Battery Numbers | 6 PCS | |
Charging Current | 5A(Default),1A-12A adjustable | |
Charging Voltage | 82.2VDC ± 1% | |
Charging Mode | 2-stage or 3-stage | |
INDICATORS | ||
LCD Panel | Load level, Battery level, AC mode, Battery mode, Bypass mode,and Fault condictions | |
ENVIRONMENT | ||
Ambient temperature | 0- 40°C | |
Operation Humidity | 20%-95% (non-condensing) | |
Storage temperature | -15~60℃ (no battery inside) | |
Altitude | <1000m ( the height above 1000m should be reduced to a maximum of 4000m.) | |
Noise Level | Less than 50dBA @ 1 Meter | |
COMMUNICATION | ||
Communication Inteface | Standard: RS232, USB; Option: Dry contact, EPO | |
Smart Slot | Optional SNMP Card |