Rack Mount UPS | 3kVA/3kW | PF 1.0 | 72Vdc | 208V/220V/230V/240V | 6x12V7AH UPS battery
Prostar PER1103B single phase rack mount online 3kva ups battery backup power supplies utility power to the connected loads in the event of a UPS power overload or fault.
PER1103B 2U rack mount online 3kva ups provides early-warning fault analysis ensuring proactive component replacement.
The PF1.0 rack mount ups provides Pure Sine Wave power output for sensitive equipment that requires smoother and cleaner input source. The pure sine wave source ensures system is operating more efficiently to reduce power consumption and save electricity costs.
1.Smart slot 10.Maintenance bypass switch (option)
2.RS-232 port 11.Cooling fan
3.Output receptacles 12.AC Input terminal
4.Ground terminal 13.AC Output terminal
5.External battery connector 14.AC Input/Output terminal
6.Emergency power off connector (option) 15.Battery pack output circuit breaker
7.USB port 16.Battery bank
8.Input circuit breaker 17.Rack mount hole
9.AC Input socket 18.Parallel operation port (option)
You can power a TV with an Uninterrupted Power Supply (UPS), and depending on the size (and cost) of the power supply it may keep the TV going for anywhere from 15 minutes to 2 hours. It’s smart to use a UPS for your TV (or other expensive electrical equipment) as cost-effective insurance.
Perhaps you weren’t aware that UPS systems represent a fire risk. But when UPS batteries are close to the end of discharging, or when they get older, their level of short circuit current falls.
PDUs merely distribute power. They do not generate it. UPSs are essentially backup batteries in the server rack. They provide backup power in the event of an outage and complete protection against power quality problems.
MODEL | PER1103B | |
CAPACITY | 3000VA / 3000W | |
Battery Voltage | 72VDC | |
Size, D X W X H (mm) | 440 X 600 X 88 | |
Net Weight (kgs) | 21.5 | |
INPUT | ||
Nominal Voltage | 208/220/230/240VAC | |
Input Voltage Range | 110-300VAC | |
Frequency Range | 50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz | |
Phase | Single Phase, L+N+PE | |
Power Factor | ≧ 0.99 @ nominal voltage (input voltage) | |
Harmonic Distortion | ≤4% (Linear Load), ≤5% (Non-linear Load) | |
OUTPUT | ||
Output voltage | 208/220/230/240VAC | |
AC Voltage Regulation | ± 1% (Batt. Mode) | |
Frequency Range(Line Mode) | Synchronized range | |
Frequency Range (Batt. Mode) | 50Hz ± 0.25Hz or 60Hz ± 0.3Hz | |
Overload Capacity | 30mins @102%-110% load 10mins @110%-130% load 30sec @130%-150% load 200ms @>150% load |
|
Current Crest Ratio | 3:1 | |
Harmonic Distortion | ≦3% THD (Linear Load);≦6% THD (Non-linear Load) | |
Transfer Time | AC Mode to Battery Mode | 0ms |
Inverter to Bypass | 4ms | |
Waveform (Batt. Mode) | Pure Sine Wave | |
EFFICIENCY | ||
AC Mode | 95.5% | |
Battery Mode | 91.5% | |
BATTERY | ||
Battery Type | 12V 7AH Lead Acid Battery | |
Battery Numbers | 6 PCS | |
Charging Current | 1A(Default), 1A-4A adjustable | |
Charging Voltage | 81VDC ± 1% | |
Charging Mode | 2-stage(CC/ Floating) or 3-stage (CC/CV/Floating) | |
INDICATORS | ||
LCD Panel | Load level, Battery level, AC mode, Battery mode, Bypass mode,and Fault conditions | |
ENVIRONMENT | ||
Ambient temperature | 0- 40°C | |
Operation Humidity | 5%-95% (non-condensing) | |
Storage temperature | -15~60℃ (no battery inside) | |
Altitude | <1000m ( the height above 1000m should be reduced to a maximum of 4000m.) | |
Noise Level | Less than 50dBA @ 1 Meter | |
COMMUNICATION | ||
Communication Interface | Standard: RS232, USB; Option: Dry contact, EPO | |
Smart Slot | Optional SNMP Card |