3 Phase Modular UPS Power Modular | 20KVA / 20KW | 3 Phases 4 Wires | 208V/220V | +/-120Vdc | Pure Sine Wave
Prostar MPS20KLV hot-swapped modular ups power module 20kW 208V 220V can provide uninterrupted, high-performance power solutions for critical applications.
The hot-swappable Power Modules allow quick maintenance and expansion. A latch located on the front of each module fixes and locks the module in its assigned slot. Each Power Module has an LED indicator to show its operation status.
Delivers a robust 20kW output in a compact form factor, optimizing space usage and reducing footprint. Each 20kW power module can be hot-swapped, allowing for seamless maintenance and scalability without interrupting the power supply.
Equipped with adaptive load management, the power module 20kVA 20kW can adjust to varying power demands, ensuring consistent performance under all conditions.
Reliable Power Protection
Designed to provide continuous power, this UPS module ensures that critical systems remain operational during outages or fluctuations, protecting sensitive equipment from power surges, dips, and blackouts.
Scalability and Flexibility
With a modular design, you can easily expand or upgrade the system by adding additional 20kW modules. This allows businesses to grow their power capacity incrementally, optimizing capital investments and future-proofing infrastructure.
Cost-Efficient Operations
High energy efficiency (up to 96%) reduces power losses and cuts down on electricity costs, making it an eco-friendly and budget-conscious choice. The advanced battery management also minimizes replacement costs by extending battery life.
Simplified Maintenance and Downtime Reduction
Hot-swappable modules mean maintenance can be done without shutting down the system, reducing downtime and ensuring seamless power continuity even during repairs or upgrades.
Enhanced Monitoring and Control
Remote monitoring and control allow users to proactively manage power usage and respond quickly to potential issues, which can minimize downtime and improve efficiency. This feature is especially valuable for facilities with high operational demands and limited on-site technical staff.
Model | MPS20KLV |
Capacity | 20kVA / 20KW |
Phase | 3-phase in / 3-phase out |
Battery Voltage | +/- 120V |
Size, D X W X H (mm) | 736.5x490x133(3U) |
Cabinet Net Weight (Kgs) | 34.5 |
INPUT | |
Input Voltage | 208VAC/220VAC(3Ph+N) |
Voltage Range | 182V~253V at 90%~100% Load; 156~253V at 63%~90% Load; 121~253Vfor <63% Load |
Nominal Frequency | 50/60Hz(Auto Sensing) |
Frequency Range | 40Hz~70Hz |
Power Factor | >0.99 @ 100% Load, >0.98 @ 50% Load |
Harmonic Distortion (THDi) | < 3% @ 100% Load |
OUTPUT | |
Nominal Voltage | 208VAC/220VAC (3Ph+N) |
Voltage Regulation(Steady state) | ≤±1%Typical(balanced Load);≤±2% Typical (unbalanced Load) |
Nominal Frequency | 50/60Hz |
Frequency Range(Synchronized) | 46Hz~54Hz or 56Hz~64Hz |
Power Factor | 1 (kVA=kW) |
Overload Capability | 1 hour for 110%, 10 mins for 120%, 1 min for 150%, 200ms for >150% |
Harmonic Distortion | ≤2% THD(Linear Load); ≤4% THD( Non-linear Load ) |
EFFICIENCY | |
Online Mode | Up to 92.5% at over 50% load |
BATTERY/CHARGER | |
Nominal Voltage | +/- 120V (12V x 20Pcs) |
Float Charging Voltage | 2.3V/Cell |
Boost Charging Voltage | 2.35V/Cell |
Temperature Compensation | Yes |
Maximum Charging Current | 8A (User adjustable) |
STANDARDS | |
Safety | UL1778, CSA C22.2 No. 107.3-05 |
EMC | FCC Part 15, Subpart B Class A |
ENVIRONMENT | |
Operation Temperature | 0~40°C |
Relative Humidity | 0~95% Non-condensing |
Altitude | <1000m for Nominal power |
IP Class | IP20 |