Industrial UPS | 60kVA / 48kW | 3 Phase | 208Vac/220Vac/440Vac/480Vac | 384Vdc
Prostar GT60K PLUS 3 phase igbt 480v ups units power supply 60kva supports three-phase power, ensuring compatibility with high-demand industrial environments. An intuitive LCD display provides real-time information on power status, load levels, battery backup time, and system settings. Additionally, remote monitoring capabilities facilitate easy management.
Its true online double-conversion technology provides superior power protection by isolating output power from input anomalies, ensuring a clean and stable power supply. The ups units power supply 60kva provides the highest level of power protection by converting incoming AC power to DC and back to AC, delivering clean and stable power to connected equipment.
IGBT Inverter Technology
Reduces total harmonic distortion (THD) to less than 2%, maintaining peak efficiency and performance of connected devices.
Built-in Isolation Transformer
Enhances power quality by providing electrical isolation and protection against electrical noise, spikes, and surges.
Zero Transfer Time
The UPS guarantees no interruption in power supply during transitions between mains and battery modes, making it ideal for mission-critical applications.
Robust Design
Built with high-quality materials, the UPS can withstand harsh environmental conditions, ensuring long-term durability and performance.
Scalability and Redundancy
The system supports N+1 or N+X redundancy configurations, allowing multiple units to operate in parallel. This feature enhances reliability and allows for capacity expansion as needed.
The GT60K PLUS 60kva ups units power supply is designed with advanced features to handle individual unit failures effectively within a parallel connection setup.
N+1 Redundancy
In a parallel configuration, the ups units power supply can be set up in an N+1 redundancy mode. This means that if one UPS unit fails, the remaining units automatically share the load, ensuring that there is no interruption in power supply to critical equipment. This redundancy minimizes the risk of downtime.
Automatic Load Redistribution
When a failure is detected in one of the connected UPS units, the system automatically redistributes the load among the operational units. This process occurs seamlessly, allowing the remaining units to compensate for the lost capacity without any manual intervention.
Fault Detection and Notification
The ups units power supply can sophisticate monitoring and diagnostic capabilities. It continuously checks the status of each connected unit. In the event of a failure, it can trigger alarms or notifications through its communication interfaces (like SNMP or RS232), alerting users to the issue promptly.
Self-Diagnosis and Recovery
After a fault occurs, the ups uninterruptible power supply conducts self-diagnosis to identify issues. Once resolved, the faulty unit can be reintegrated into the parallel system without requiring a complete shutdown of the other units.
Model | GT60K PLUS |
Capacity | 60KVA/48KW |
UPS Efficiency | >95% |
Noise | 53dB~62dB(Distance 1 Meter) |
Dimension(WxDxH mm) | 905x740x1220 |
Weight(Kgs) | 655 |
INPUT | |
Voltage | 3 Phases 4 Wires, 208Vac/220Vac/440Vac/480Vac ± 25% |
Frequency | 50Hz/60Hz±5% (Automatically) |
Power Factor | ≥0.95 |
OUTPUT | |
Voltage | 3 Phases 4 Wires, 208Vac/220Vac/440Vac/480Vac ± 1% |
Frequency | 50Hz/60Hz±0.05%(By Battery) |
Harmonic Distortion | Linear load<3%, Non-linear load<5% |
Imbalance Voltage | Balance load≤1%, Imbalance load≤3% |
Phase Shift Angle | Balance load≤1°, Imbalance load≤2° |
Transient Response | Output at 0~50%~100% ≤5%, response ≤ 10ms |
Overload Capacity | 110%≥300Min, 125%≥10Min, 150%≥1Min |
Crest Factor | 3:1 |
Wave Form | Pure sine wave |
Transfer Time | 0ms |
BATTERY | |
Type | Support VRLA Battery |
D.C. Voltage | 384Vdc |
Max. Charging Current | 0.2AxC10 |
Charging Time(Standard) | 12hours |
SYSTEM | |
Protection | Input over-voltage, under-voltage; output overload, shortcircuit; Inverter over-temperature; Battery under-voltage,over-voltage |
IP Protection | IP20 |
Parallel Mode | N+1,N+X,can be in parallel with different power capacity |
Software Interface | Windows9x,2000,NT,ME,XP,Linux,Novell,Macosx,NT4.0 |
Meantime Between Failures | 300,000Hours |
ENVIRONMENT | |
Operating Temperature | 0℃ to 40℃ |
Humidity | 0~95% (non-condensing) |
Altitude | <1000m (with increase of 100m,it will reduce output of 1%) max. 4000m |
Storage Temperature | -25℃ to 55℃ |
MANAGEMENT | |
Communication Interface | RS232/RS485 |
Remote Signaling | Dry contact (battery low,battery discharging,bypass/fault),EPO |
Remote Control | EPO and bypass |
SNMP Card | Power management from SNMP manager and web browser |