Industrial UPS | 80kVA / 64kW | 3 Phase | 208Vac/220Vac/440Vac/480Vac | 384Vdc
Prostar GT80K PLUS 80kva smart uninterruptible power supply 480vac ups can provide reliable and efficient power protection for critical applications. Operating at 480VAC, this UPS solution integrates several cutting-edge technologies to ensure maximum uptime and efficiency.
At its core, the 80kva smart uninterruptible power supply 480vac ups features an isolation transformer that provides galvanic separation between the input and output. It can reduce the risk of electrical noise and interference affecting sensitive equipment. This feature also contributes to enhanced safety and stability across the system.
IGBT Inverter Technology
Equipped with advanced Insulated Gate Bipolar Transistor (IGBT) technology, the GT80K PLUS offers superior performance and efficiency. The IGBT module enables fast switching capabilities, reducing energy losses and improving the overall efficiency of the UPS system.
Built-in Isolation Transformer
Enhances power quality by providing electrical isolation and protection against electrical noise, spikes, and surges.
Double Online Configuration
The double online architecture of the smart uninterruptible power supply ensures that the UPS operates in a true online mode, providing continuous power to connected devices. This configuration guarantees zero transfer time during power outages, ensuring that critical loads remain powered without interruption.
Powerful Communication System
The uninterruptible power supply ups system features a powerful communication system that allows for seamless integration with various monitoring and management tools. Users can easily monitor the UPS status, receive alerts, and manage settings remotely, enhancing operational efficiency and reliability.
Scalability and Redundancy
The system supports N+1 or N+X redundancy configurations, allowing multiple units to operate in parallel. This feature enhances reliability and allows for capacity expansion as needed.
The smart uninterruptible power supply is designed with advanced features to handle individual unit failures effectively within a parallel connection setup.
N+1 Redundancy
In a parallel configuration, the ups units power supply can be set up in an N+1 redundancy mode. This means that if one UPS unit fails, the remaining units automatically share the load, ensuring that there is no interruption in power supply to critical equipment. This redundancy minimizes the risk of downtime.
Automatic Load Redistribution
When a failure is detected in one of the connected UPS units, the system automatically redistributes the load among the operational units. This process occurs seamlessly, allowing the remaining units to compensate for the lost capacity without any manual intervention.
Fault Detection and Notification
The ups units power supply can sophisticate monitoring and diagnostic capabilities. It continuously checks the status of each connected unit. In the event of a failure, it can trigger alarms or notifications through its communication interfaces (like SNMP or RS232), alerting users to the issue promptly.
Self-Diagnosis and Recovery
After a fault occurs, the ups uninterruptible power supply conducts self-diagnosis to identify issues. Once resolved, the faulty unit can be reintegrated into the parallel system without requiring a complete shutdown of the other units.
Model | GT80K PLUS |
Capacity | 80KVA/64KW |
UPS Efficiency | >95% |
Noise | 53dB~62dB(Distance 1 Meter) |
Dimension(WxDxH mm) | 1450x750x1400 |
Weight(Kgs) | 905 |
INPUT | |
Voltage | 3 Phases 4 Wires, 208Vac/220Vac/440Vac/480Vac ± 25% |
Frequency | 50Hz/60Hz±5% (Automatically) |
Power Factor | ≥0.95 |
OUTPUT | |
Voltage | 3 Phases 4 Wires, 208Vac/220Vac/440Vac/480Vac ± 1% |
Frequency | 50Hz/60Hz±0.05%(By Battery) |
Harmonic Distortion | Linear load<3%, Non-linear load<5% |
Imbalance Voltage | Balance load≤1%, Imbalance load≤3% |
Phase Shift Angle | Balance load≤1°, Imbalance load≤2° |
Transient Response | Output at 0~50%~100% ≤5%, response ≤ 10ms |
Overload Capacity | 110%≥300Min, 125%≥10Min, 150%≥1Min |
Crest Factor | 3:1 |
Wave Form | Pure sine wave |
Transfer Time | 0ms |
BATTERY | |
Type | Support VRLA Battery |
D.C. Voltage | 384Vdc |
Max. Charging Current | 0.2AxC10 |
Charging Time(Standard) | 12hours |
SYSTEM | |
Protection | Input over-voltage, under-voltage; output overload, shortcircuit; Inverter over-temperature; Battery under-voltage,over-voltage |
IP Protection | IP20 |
Parallel Mode | N+1,N+X,can be in parallel with different power capacity |
Software Interface | Windows9x,2000,NT,ME,XP,Linux,Novell,Macosx,NT4.0 |
Meantime Between Failures | 300,000Hours |
ENVIRONMENT | |
Operating Temperature | 0℃ to 40℃ |
Humidity | 0~95% (non-condensing) |
Altitude | <1000m (with increase of 100m,it will reduce output of 1%) max. 4000m |
Storage Temperature | -25℃ to 55℃ |
MANAGEMENT | |
Communication Interface | RS232/RS485 |
Remote Signaling | Dry contact (battery low,battery discharging,bypass/fault),EPO |
Remote Control | EPO and bypass |
SNMP Card | Power management from SNMP manager and web browser |