GT50K PLUS 480v output ups uninterrupted power supply 50kVA

Industrial UPS | 50kVA / 40kW | 3 Phase | 208Vac/220Vac/440Vac/480Vac | 384Vdc

SKU: GT50K PLUS Category:

Prostar GT50K PLUS 480v output ups uninterrupted power supply 50kVA ensures optimal performance and protection for your sensitive equipment.  This UPS is suitable for medium to large-scale applications such as data centers, telecommunications, and industrial environments.

Its true online double-conversion technology provides superior power protection by isolating output power from input anomalies, ensuring a clean and stable power supply. UPS uninterrupted power supply 50kVA delivers 480V three-phase power, compatible with high-demand industrial environments. Minimizes total harmonic distortion (THD) to less than 2%, maintaining peak efficiency and performance of connected equipment.

 

GT50K PLUS 480v output ups uninterrupted power supply 50kVA

 

UPS Uninterrupted Power Supply 50kVA Features

Advanced IGBT Technology

Utilizing Insulated Gate Bipolar Transistor (IGBT) technology, the UPS minimizes total harmonic distortion (THD) to less than 2%, ensuring optimal performance for sensitive electronic equipment.

Pure Sine Wave Output

Delivers clean power that is compatible with a wide range of electronic equipment.

Zero Transfer Time

The UPS guarantees no interruption in power supply during transitions between mains and battery modes, making it ideal for mission-critical applications.

Comprehensive Protection

The ups uninterrupted power supply includes multiple protection mechanisms such as input over-voltage, under-voltage, output overload, short circuit protection, and battery overcharging safeguards.

Scalability and Redundancy

The system supports N+1 or N+X redundancy configurations, allowing multiple units to operate in parallel. This feature enhances reliability and allows for capacity expansion as needed.

Network-Based Power Management

Supports SNMP for remote monitoring and management, allowing for easy integration into existing network infrastructure.

UPS Backup Power Supply Diagram

GT PLUS UPS 480V 3 Phase Diagram

Online UPS Touch LCD Information

Industrial UPS System Inner Components View

Prostar 3 Phase Online UPS Isolation Transformer

Three Phase UPS Parallel Connection

The GT50K PLUS UPS features a robust parallel connection capability that enhances its performance and reliability.

Scalability

The ups uninterrupted power supply 50kVA allows multiple units to be connected in parallel, enabling users to scale their power capacity as needed. This is particularly beneficial for growing operations that may require additional power support in the future.

Redundancy

By connecting several UPS units in parallel, the system can provide N+1 redundancy. This means that if one unit fails, the remaining units can take over the load without any interruption in power supply, ensuring continuous operation for critical applications.

Load Balancing

The parallel configuration ensures that the load is evenly distributed among all connected UPS units. This helps in optimizing performance and prolonging the lifespan of each unit by preventing any single unit from being overloaded.

Synchronization

The GT50K PLUS 50kVA uninterruptible power supply ensures that all units in a parallel setup operate synchronously. This synchronization is crucial for maintaining a stable output voltage and frequency, which protects sensitive equipment from potential damage due to power fluctuations.

The Articles You may Like

 

 

Model GT50K PLUS
Capacity 50KVA/40KW
UPS Efficiency >95%
Noise 53dB~62dB(Distance 1 Meter)
Dimension(WxDxH mm) 905x740x1220
Weight(Kgs) 575
INPUT
Voltage 3 Phases 4 Wires, 208Vac/220Vac/440Vac/480Vac ± 25%
Frequency 50Hz/60Hz±5% (Automatically)
Power Factor ≥0.95
OUTPUT
Voltage 3 Phases 4 Wires, 208Vac/220Vac/440Vac/480Vac ± 1%
Frequency 50Hz/60Hz±0.05%(By Battery)
Harmonic Distortion Linear load<3%, Non-linear load<5%
Imbalance Voltage Balance load≤1%, Imbalance load≤3%
Phase Shift Angle Balance load≤1°, Imbalance load≤2°
Transient Response Output at 0~50%~100% ≤5%, response ≤ 10ms
Overload Capacity 110%≥300Min, 125%≥10Min, 150%≥1Min
Crest Factor 3:1
Wave Form Pure sine wave
Transfer Time 0ms
BATTERY
Type Support VRLA Battery
D.C. Voltage 384Vdc
Max. Charging Current 0.2AxC10
Charging Time(Standard) 12hours
SYSTEM
Protection Input over-voltage, under-voltage; output overload, shortcircuit; Inverter over-temperature; Battery under-voltage,over-voltage
IP Protection IP20
Parallel Mode N+1,N+X,can be in parallel with different power capacity
Software Interface Windows9x,2000,NT,ME,XP,Linux,Novell,Macosx,NT4.0
Meantime Between Failures 300,000Hours
ENVIRONMENT
Operating Temperature 0℃ to 40℃
Humidity 0~95% (non-condensing)
Altitude <1000m (with increase of 100m,it will reduce output of 1%) max. 4000m
Storage Temperature -25℃ to 55℃
MANAGEMENT
Communication Interface RS232/RS485
Remote Signaling Dry contact (battery low,battery discharging,bypass/fault),EPO
Remote Control EPO and bypass
SNMP Card Power management from SNMP manager and web browser