Modular UPS Systems | 60KVA / 60KW | 3 Phase 4 Wires | 3 x 20KW Power Module
Prostar MPS60K-15U scalable modular data center ups power 60kva is a highly reliable and scalable modular UPS system designed to ensure seamless power protection for data centers and critical infrastructure.
The data center ups power 60kva can work with scalability in mind, allowing users to incrementally increase their power capacity as their data center grows, without the need for complete system replacement. This modular approach minimizes downtime and maximizes return on investment.
Leveraging advanced technology, this scalable data center UPS operates at an impressive efficiency level, reducing energy consumption and operational costs. It features an eco-mode that further enhances efficiency by bypassing the inverter during stable utility conditions, while still providing protection against surges and spikes.
Compact Design
Despite its robust power output, the modular UPS boasts a compact footprint that is ideal for space-constrained environments. You can configure it in a rack-mount or stand-alone configuration, making it adaptable to various installation requirements.
High Efficiency Online Double Conversion Technology
By utilizing online double conversion technology, the data center ups achieves high power efficiency while delivering a pure sine wave output, ensuring stable power for sensitive equipment.
Output Power Factor 1
This system provides a unity power factor (PF 1.0), maximizing power output efficiency and effectively supporting all connected loads.
Multi-Level Protection
The UPS system provides multi-level protection against electrical anomalies such as voltage spikes, sags, and surges. This ensures that connected equipment receives clean power, reducing the risk of damage from power disturbances.
Communication Interfaces
Equipped with multiple communication ports, including RS232, USB, Ethernet, and serial connections, the UPS allows for seamless integration with existing infrastructure and monitoring systems. Optional SNMP cards enable remote monitoring and management over a network.
Audible Alarms and LED Indicators
Clear audible alarms and visual indicators provide immediate feedback about the UPS’s status and any potential issues, alerting operators to take corrective actions promptly.
Adjustable Battery Numbers
The flexibility to adjust the number of batteries allows for custom power configurations, optimizing battery usage and storage.
1+1 Cabinets Parallel Support
For enhanced redundancy and capacity expansion, the modular ups power supports parallel operation in a 1+1 cabinet configuration, providing scalable power solutions for growing infrastructure.
In the front of the UPS, there are control interface (LCD Panel), communication slots, communication ports and 3 Power Module slots.
All wiring terminal blocks are allocated in the back of cabinet. The side panels are locked by screws. The casters at the bottom of the UPS cabinet can be used to move over for short distances. There are two leveling feet to fix and stabilize the UPS cabinet on the ground.
When discussing the wiring terminal blocks of a modular UPS like the MPS60K-15U, it’s important to understand how these components facilitate the connection and management of power distribution. The terminal blocks serve as the points where wires are connected to the UPS for both input and output power, as well as for optional auxiliary functions such as battery connections and external monitoring devices.
When connecting wires to the terminal blocks, ensure that:
External Battery Connection
External batteries can extend the runtime of the UPS significantly, depending on the capacity and number of batteries installed.
The 20 kVA Power Module has independent hardware and controllability, able to operate and coordinate with other modules within the system. See details:
MPS20K scalable three phase modular ups system 20 kW power module
Warning: The power modules installed in the same cabinet must be at the same rating.
Cabinet Model | MPS60K-15U |
Maximum Capacity | 60KW |
Phase | 3-phase in / 3-phase out |
Battery Voltage | +/- 216V Default, +/- 192V or +/- 240V Selectable |
Power Module Capacity | 20kVA / 20KW |
Number of Power Modules | 3 Pcs |
Size, D X W X H (mm) | 1000X515X763 |
Cabinet Net Weight (Kgs) | 182 |
INPUT | |
Input Voltage | 380VAC/400VAC/415VAC (3Ph+N) |
Voltage Range | 305~477VAC at 70%~100% Load; 208~478VAC for <70% Load |
Nominal Frequency | 50/60Hz(Auto Sensing) |
Frequency Range | 40Hz~70Hz |
Power Factor | >0.99 @ 100% Load, >0.98 @ 50% Load |
Harmonic Distortion (THDi) | < 3% @ 100% Load |
OUTPUT | |
Nominal Voltage | 380VAC/400VAC/415VAC (3Ph+N) |
Voltage Regulation(Steady state) | ≤±1%Typical(Balanced Load);≤±2% Typical (Unbalanced Load) |
Nominal Frequency | 50/60Hz |
Frequency Range(Synchronized) | 46Hz~54Hz or 56Hz~64Hz |
Power Factor | 1 (kVA=kW) |
Overload Capability | 1 hour for 110%, 10 mins for 120%, 1 min for 150%, 200ms for >150% |
Harmonic Distortion | ≤2% THD(Linear Load); ≤4% THD( Non-linear Load ) |
EFFICIENCY | |
Online Mode | Up to 94.5% |
BATTERY/CHARGER | |
Nominal Voltage | +/- 216V (12V x 36Pcs) |
Maximum Voltage | +/- 240V (12V x 40Pcs) |
Minimum Voltage | +/- 192V (12V x 32Pcs) |
Float Charging Voltage | 2.25V/Cell |
Boost Charging Voltage | 2.35V/Cell |
Temperature Compensation | Yes |
Maximum Charging Current | 6A for each power module (User adjustable) |
STANDARDS | |
Safety | IEC/EN 60950-1; IEC/EN 62040-1 |
EMC | IEC/EN 62040-2 Category C3 |
ENVIRONMENT | |
Operation Temperature | 0~40°C |
Relative Humidity | 0~95% Non-condensing |
Altitude | <1000m for Nominal power |
IP Class | IP20 |
MANAGEMENT | |
Communication Interface | Dry Contact, RS-232, USB, SNMP Slot |
Smart RS-232 or USB | Windows® 2000/2003/XP/Vista/2008、Windows® 7/8、Linux、Unix、MAC |
Optional SNMP | Power management from SNMP manager and web browser |