Rack Mount UPS | 2kVA/2kW | PF 1.0 | 72Vdc | 208V/220V/230V/240V | Without battery inside
Prostar PER1102 best 220v rack mount pure sine wave 2000va ups power source provides management of the UPS via a smart slot.
PER1102 rack mount 2000va ups adopts advanced technology to enhance UPS operating efficiency, reduce heat generation, consume less power and save more energy costs.
The ECO and frequency inverter operation modes highlight the requirements for a modern versatile UPS.
The PF1.0 rack mount ups provides Pure Sine Wave power output for sensitive equipment that requires smoother and cleaner input source.
2U rack mount 2000va UPS avoids costly power problems by keeping your IT equipment and data protected and available.
1.Smart slot 10.Maintenance bypass switch (option)
2.RS-232 port 11.Cooling fan
3.Output receptacles 12.AC Input terminal
4.Ground terminal 13.AC Output terminal
5.External battery connector 14.AC Input/Output terminal
6.Emergency power off connector (option) 15.Battery pack output circuit breaker
7.USB port 16.Battery bank
8.Input circuit breaker 17.Rack mount hole
9.AC Input socket 18.Parallel operation port (option)
A rack mount UPS supplies uninterrupted power to the connected devices in the event of a power failure, thereby preventing failure of equipment and loss of data. A rack mount UPS is ideal for workplaces with networking and server applications.
An uninterruptible power supply (UPS) is an electrical setup that provides power backup when the main power source fails. It is commonly used to protect hardware such as computers, telecommunication equipment, and other sensitive electronics.
PDUs merely distribute power. They do not generate it. UPSs are essentially backup batteries in the server rack. They provide backup power in the event of an outage and complete protection against power quality problems.
MODEL | PER1102 | |
CAPACITY | 2000VA / 2000W | |
Battery Voltage | 48VDC/72VDC(default) | |
Size, D X W X H (mm) | 440x420x88 | |
Net Weight (kgs) | 6.5 | |
INPUT | ||
Nominal Voltage | 208/220/230/240VAC | |
Input Voltage Range | 110-300VAC | |
Frequency Range | 50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz | |
Phase | Single Phase, L+N+PE | |
Power Factor | ≧ 0.99 @ nominal voltage (input voltage) | |
Harmonic Distortion | ≤4% (Linear Load), ≤5% (Non-linear Load) | |
OUTPUT | ||
Output voltage | 208/220/230/240VAC | |
AC Voltage Regulation | ± 1% (Batt. Mode) | |
Frequency Range(Line Mode) | Synchronized range | |
Frequency Range (Batt. Mode) | 50Hz ± 0.25Hz or 60Hz ± 0.3Hz | |
Overload Capacity | 30mins @102%-110% load 10mins @110%-130% load 30sec @130%-150% load 200ms @>150% load |
|
Current Crest Ratio | 3:1 | |
Harmonic Distortion | ≦3% THD (Linear Load);≦6% THD (Non-linear Load) | |
Transfer Time | AC Mode to Battery Mode | 0ms |
Inverter to Bypass | 4ms | |
Waveform (Batt. Mode) | Pure Sine Wave | |
EFFICIENCY | ||
AC Mode | 95.5% | |
Battery Mode | 91.5% | |
BATTERY | ||
Battery Type | Depending on applications | |
Battery Numbers | 6 PCS | |
Charging Current | 5A(Default),1A-12A adjustable | |
Charging Voltage | 81VDC ± 1% | |
Charging Mode | 2-stage(CC/ Floating) or 3-stage (CC/CV/Floating) | |
INDICATORS | ||
LCD Panel | Load level, Battery level, AC mode, Battery mode, Bypass mode,and Fault conditions | |
ENVIRONMENT | ||
Ambient temperature | 0- 40°C | |
Operation Humidity | 5%-95% (non-condensing) | |
Storage temperature | -15~60℃ (no battery inside) | |
Altitude | <1000m ( the height above 1000m should be reduced to a maximum of 4000m.) | |
Noise Level | Less than 50dBA @ 1 Meter | |
COMMUNICATION | ||
Communication Interface | Standard: RS232, USB; Option: Dry contact, EPO | |
Smart Slot | Optional SNMP Card |