Rack Mount UPS | 2kVA/2kW | PF 1.0 | 48Vdc | 208V/220V/230V/240V | 4x12V7AH UPS battery
Prostar PER1102B 2U single phase 2kva rack mount 48v ups battery backup can equalize the voltage of each individual battery, getting the most out of it..
PER1102B 2kva rack mount 48v ups battery backup adopts advanced technology to enhance UPS operating efficiency, reduce heat generation, consume less power and save more energy costs.
The ECO and frequency inverter operation modes highlight the requirements for a modern versatile UPS.
The PF1.0 rack mount ups provides Pure Sine Wave power output for sensitive equipment that requires smoother and cleaner input source.
The LCD readout displays clear system information, such as power status, battery status, load status and more. It also features a user-friendly and intuitive interface, allowing users to easily manage and monitor the entire system.
1.Smart slot 10.Maintenance bypass switch (option)
2.RS-232 port 11.Cooling fan
3.Output receptacles 12.AC Input terminal
4.Ground terminal 13.AC Output terminal
5.External battery connector 14.AC Input/Output terminal
6.Emergency power off connector (option) 15.Battery pack output circuit breaker
7.USB port 16.Battery bank
8.Input circuit breaker 17.Rack mount hole
9.AC Input socket 18.Parallel operation port (option)
It’s very rare, but there is a possibility of electrolyte leakage from inside of lead acid batteries by such as manufacturing defects. If leakage from battery occurs, a ground fault accident occurs, and may cause serious accidents.
An uninterruptible power supply (UPS) is an electrical setup that provides power backup when the main power source fails. It is commonly used to protect hardware such as computers, telecommunication equipment, and other sensitive electronics.
PDUs merely distribute power. They do not generate it. UPSs are essentially backup batteries in the server rack. They provide backup power in the event of an outage and complete protection against power quality problems.
MODEL | PER1102B | |
CAPACITY | 2000VA / 2000W | |
Battery Voltage | 48VDC | |
Size, D X W X H (mm) | 440x420x88 | |
Net Weight (kgs) | 17 | |
INPUT | ||
Nominal Voltage | 208/220/230/240VAC | |
Input Voltage Range | 110-300VAC | |
Frequency Range | 50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz | |
Phase | Single Phase, L+N+PE | |
Power Factor | ≧ 0.99 @ nominal voltage (input voltage) | |
Harmonic Distortion | ≤4% (Linear Load), ≤5% (Non-linear Load) | |
OUTPUT | ||
Output voltage | 208/220/230/240VAC | |
AC Voltage Regulation | ± 1% (Batt. Mode) | |
Frequency Range(Line Mode) | Synchronized range | |
Frequency Range (Batt. Mode) | 50Hz ± 0.25Hz or 60Hz ± 0.3Hz | |
Overload Capacity | 30mins @102%-110% load 10mins @110%-130% load 30sec @130%-150% load 200ms @>150% load |
|
Current Crest Ratio | 3:1 | |
Harmonic Distortion | ≦3% THD (Linear Load);≦6% THD (Non-linear Load) | |
Transfer Time | AC Mode to Battery Mode | 0ms |
Inverter to Bypass | 4ms | |
Waveform (Batt. Mode) | Pure Sine Wave | |
EFFICIENCY | ||
AC Mode | 95.5% | |
Battery Mode | 91.5% | |
BATTERY | ||
Battery Type | 12V 7AH Lead Acid Battery | |
Battery Numbers | 4 PCS | |
Charging Current | 1A(Default), 1A-4A adjustable | |
Charging Voltage | 54VDC ± 1% | |
Charging Mode | 2-stage(CC/ Floating) or 3-stage (CC/CV/Floating) | |
INDICATORS | ||
LCD Panel | Load level, Battery level, AC mode, Battery mode, Bypass mode,and Fault conditions | |
ENVIRONMENT | ||
Ambient temperature | 0- 40°C | |
Operation Humidity | 5%-95% (non-condensing) | |
Storage temperature | -15~60℃ (no battery inside) | |
Altitude | <1000m ( the height above 1000m should be reduced to a maximum of 4000m.) | |
Noise Level | Less than 50dBA @ 1 Meter | |
COMMUNICATION | ||
Communication Interface | Standard: RS232, USB; Option: Dry contact, EPO | |
Smart Slot | Optional SNMP Card |