Double Conversion UPS | 2000VA / 2000W | 48Vdc | 208V/220V/230V/240V | Built-in 4 x12V7AH UPS battery
Prostar PET1102B 48v double conversion online 2kva ups backup power system is a transformer-less UPS that combines high efficiency values with compact footprint and flexible configurations.
PET1102B high frequency 2KVA UPS also has USB and RS-232 communication ports as standard, with a built-in intelligent slot for additional adapters, protocol converters and relate contact cards.
Double conversion online UPS 2kVA provides clean, stable power to connected devices by converting incoming AC power to DC power, and then back to AC power. This conversion process ensures that the output voltage is consistently regulated, free from voltage fluctuations and surges, and provides protection against power outages and other electrical disturbances.
There are several advantages of a modular UPS:
– With a modular UPS power backup system, the power modules can be switched to either higher or lower capacity as desired.
– Modular UPS systems provide better efficiency with reduced repair time. Stocking a spare power module at a site can save repair time immensely.
Yes, it is possible to monitor the UPS through your computer via the RS232 or USB ports which are a standard built-in feature in the new-age UPS power backup systems. It is also possible to monitor the UPS over a network with the help of an optional SNMP/ Network card. UPS software is available for free download if you wish to access the information online. Automatic SMS/ Email alerts can be set for intimation of any status change in the functioning of the UPS.
UPS systems can be used anywhere that needs to ensure that the power keeps on following. The most common applications are where power is critical to avoid infrastructure damage, like in a data center or manufacturing facility.
MODEL | PET1102B | |
CAPACITY | 2000VA / 2000W | |
Battery Voltage | 48VDC | |
Size, D X W X H (mm) | 395 X 143 X 222 | |
Net Weight (kgs) | 14 | |
INPUT | ||
Norminal Voltage | 208/220/230/240VAC | |
Input Voltage Range | 110-300VAC | |
Frequency Range | 50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz | |
Phase | Single Phase, L+N+PE | |
Power Factor | ≧ 0.99 @ nominal voltage (input voltage) | |
Harmonic Distortion | ≤4% (Linear Load), ≤5% (Non-linear Load) | |
OUTPUT | ||
Output voltage | 208/220/230/240VAC | |
AC Voltage Regulation | ± 1% (Batt. Mode) | |
Frequency Range(Line Mode) | Synchronized range | |
Frequency Range (Batt. Mode) | 50 Hz or 60Hz ± 0.1% | |
Overload Capacity | AC Mode: Battery Mode: 30mins @102%-110% load 1min @102%-110% load 10mins @110%-130% load 10sec @110%-130% load 30sec @130%-150% load 3sec @110%-130% load 200ms @>150% load 200ms @>150% load |
|
Current Crest Ratio | 3:1 | |
Harmonic Distortion | ≦3% THD (Linear Load);≦5% THD (Non-linear Load) | |
Transfer Time | AC Mode to Battery Mode | 0ms |
Inverter to Bypass | 4ms | |
Waveform (Batt. Mode) | Pure Sine Wave | |
EFFICIENCY | ||
AC Mode | 95.5% | |
Battery Mode | 89.5% | |
BATTERY | ||
Battery Type | Sealed Maintenance-free | |
Battery Numbers | 4 PCS x 12V7AH | |
Charging Current | 1A(Default),1A-4A adjustable | |
Charging Voltage | 54.8VDC ± 1% | |
Charging Mode | 2-stage or 3-stage | |
INDICATORS | ||
LCD Panel | Load level, Battery level, AC mode, Battery mode, Bypass mode,and Fault condictions | |
ENVIRONMENT | ||
Ambient temperature | 0- 40°C | |
Operation Humidity | 20%-95% (non-condensing) | |
Storage temperature | -15~60℃ (no battery inside) | |
Altitude | <1000m ( the height above 1000m should be reduced to a maximum of 4000m.) | |
Noise Level | Less than 50dBA @ 1 Meter | |
COMMUNICATION | ||
Communication Inteface | Standard: RS232, USB; Option: Dry contact, EPO | |
Smart Slot | Optional SNMP Card |