Double Conversion UPS | 10KVA / 10KW | 192Vdc | 208V/220V/230V/240V | Built-in 16 x12V7AH UPS battery
Prostar PET1110B best online 10kva ups battery backup power supply for home offers complete power protection for critical server, network and telecommunications.
PET1110B 10kva ups battery backup power supply offers complete power protection for critical network applications.
Single Phase 10kVA Online UPS is a reliable and efficient power protection solution that ensures uninterrupted power supply to your critical equipment. With its high capacity, user-friendly interface, and double conversion technology, it is an ideal choice for businesses and organizations that require a robust and dependable power backup system.
Backup power is a term that simply means, a source of power if the mains power fails. This can be anything from some batteries in your mains powered alarm clock to UPS system and standby generator that are connected to your data centre.
An external environmental sensor will provide you with all information regarding the temperature and humidity around the UPS. You could access the same via the SNMP/ Network card.
If the power requirement is low and the UPS is overrated, possibly, but normally running a UPS for this long requires so many UPS batteries it becomes unfeasible both financial and physically. It would be best to run a standby generator alongside your UPS to achieve this.
MODEL | PET1110B | |
CAPACITY | 10000VA / 10000W | |
Battery Voltage | 192VDC | |
Size, D X W X H (mm) | 475 X 190 X 696 | |
Net Weight (kgs) | 53 | |
INPUT | ||
Norminal Voltage | 208/220/230/240VAC | |
Input Voltage Range | 110-300VAC | |
Frequency Range | 50Hz:44Hz~56Hz or 60Hz:54Hz~66Hz | |
Phase | Single Phase, L+N+PE | |
Power Factor | ≧ 0.99 | |
Harmonic Distortion | ≤5% (Linear Load), ≤8% (Non-linear Load) | |
OUTPUT | ||
Output voltage | 208/220/230/240VAC | |
AC Voltage Regulation | ± 1% (Batt. Mode) | |
Frequency Range(Line Mode) | Synchronized range | |
Frequency Range (Batt. Mode) | 50 Hz or 60Hz ± 0.1% | |
Overload Capacity | AC Mode: Battery Mode: 30mins @102%-110% load 10mins @102%-110% load 10mins @110%-130% load 1min @110%-130% load 30sec @130%-150% load 10sec @110%-130% load 500ms @>150% load 500ms @>150% load |
|
Current Crest Ratio | 3:1 | |
Harmonic Distortion | ≦2% THD (Linear Load);≦5% THD (Non-linear Load) | |
Transfer Time | AC Mode to Battery Mode | 0ms |
Inverter to Bypass | 0ms | |
Waveform (Batt. Mode) | Pure Sine Wave | |
EFFICIENCY | ||
AC Mode | 95.5% | |
Battery Mode | 95.3% | |
BATTERY | ||
Battery Type | Sealed Maintenance-free | |
Battery Numbers | 16PCS x 12V7AH | |
Charging Current | 1A(Default),1A-4A adjustable | |
Charging Voltage | 219.2VDC ± 1% | |
Charging Mode | 2-stage or 3-stage | |
INDICATORS | ||
LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault condictions | |
ENVIRONMENT | ||
Ambient temperature | 0- 40°C | |
Operation Humidity | 20%-95% (non-condensing) | |
Storage temperature | -15~60℃ (no battery inside) | |
Altitude | <1000m ( the height above 1000m should be reduced to a maximum of 4000m.) | |
Noise Level | Less than 50dBA @ 1 Meter | |
COMMUNICATION | ||
Communication Inteface | Standard: RS232, USB; Option: Dry contact, EPO | |
Smart Slot | Optional SNMP Card |