Line Interactive UPS | 500VA / 300W | 12VDC | 220Vad/230Vac/240Vac | 2U - Rack Mount | Without Battery Inside
PLR0.5K 12v single phase line interactive rack mount small ups 500va offers complete power protection for small network applications, including telecom, security and digital signage.
Prostar Line interactive UPS is a full digital control of the design concept, application of intelligent CPU control System, combined with CMOS and PWM perfect, adopt frequency online interactive structure, built in power Intelligent charger novel uninterruptible power supply products.
Line-interactive UPS systems use automatic voltage regulation (AVR) to correct abnormal voltages without switching to battery.
Power Amplifier Over Current | E01 |
Output Short Circuit Protection | E02 |
Overload Protection | E03 |
Over Temperature Protection | E04 |
Battery Over Voltage Protection | E05 |
Low Battery Voltage Protection | E06 |
Phase Reverse Protection | E07 |
Low Output Voltage Protection | E08 |
Model | PLR0.5K | |||||
Rated Power | 500VA/300W | |||||
INPUT | ||||||
Voltage Range | 100V/110V/120V/127AC or 208V/220V/230V/240VAC(+25%,-36%) | |||||
Frequency Range | 50/60 Hz±2.5Hz Auto | |||||
OUTPUT | ||||||
AC Voltage Regulation | 100V/110V/120V/127AC±0.5% or 208V/220V/230V/240VAC±0.5%(AC Mode±10%) | |||||
Frequency | 50HZ/60HZ±0.5HZ Auto(AC Mode±2.5HZ) | |||||
Surge Power | 900W | |||||
Battery Efficiency | 81% | |||||
AC Efficiency | 93% | |||||
Transfer Time | 8ms default, 4ms optional | |||||
Waveform | Pure Sinewave | |||||
BATTERY | ||||||
Battery Voltage | 12VDC | |||||
Floating Charge Voltage | 13.6VDC | |||||
Overcharge Protection | 15.0VDC | |||||
AC Charge Current | 0-20A Adjustable (20A default) | |||||
PROTECTION | ||||||
Battery Reversal | Optional | |||||
Output Short Circuit | AC mode:Jump fuse, UPS mode: Shut down | |||||
Overload | Full load 100%, UPS alarm. Overload 120%, UPS shut down output in 10s. Once the load back to normal, UPS recover output. | |||||
High AC Voltage | Turn off AC,turn to UPS mode automatically | |||||
Low DC Voltage | UPS shut down automatically,Once the AC recover, UPS turn on and charge automatically | |||||
Over Temperature | Power Off | |||||
ENVIRONMENT | ||||||
Humidity | 15~93%(No condensation) | |||||
Temperature | -10℃ ~ 50℃ | |||||
Altitude | ≤3000m | |||||
Communication | RS232(default),USB, 485, SNMP (Optional) | |||||
MECHANICAL SPECIFICATIONS | ||||||
Dimension, DxWxH (mm) | 483×390×88 [2U] | |||||
Net Weight (Kgs/PC) | 6.80 |