Line Interactive UPS | 1500VA / 900W | 24VDC | 220Vad/230Vac/240Vac | 2U - Rack Mount | Without Battery Inside
PLR1.5K 24v power supply line interactive 2u rack mount ups 1500va safeguards servers and network storage devices by providing battery backup and AC power protection. This line interactive ups is ideal protection for point-of-sale and kiosk applications, a small business VoIP network, or rack-mount equipment in your server room or network closet.
Prostar Line interactive UPS is a full digital control of the design concept, application of intelligent CPU control System, combined with CMOS and PWM perfect, adopt frequency online interactive structure, built in power Intelligent charger novel uninterruptible power supply products.
Rack mount ups 1500va protects connected mission-critical equipment against damage, downtime and data loss due to blackouts, brownouts, power surges and line noise. Ideal solution for servers, storage devices and telecom hardware.
Line-interactive UPS systems use automatic voltage regulation (AVR) to correct abnormal voltages without switching to battery.
Power Amplifier Over Current | E01 |
Output Short Circuit Protection | E02 |
Overload Protection | E03 |
Over Temperature Protection | E04 |
Battery Over Voltage Protection | E05 |
Low Battery Voltage Protection | E06 |
Phase Reverse Protection | E07 |
Low Output Voltage Protection | E08 |
Model | PLR1.5K | ||||||||||
Rated Power | 1.5KVA/900W | ||||||||||
INPUT | |||||||||||
Voltage Range | 100V/110V/120V/127AC or 208V/220V/230V/240VAC(+25%,-36%) | ||||||||||
Frequency Range | 50/60 Hz±2.5Hz Auto | ||||||||||
OUTPUT | |||||||||||
AC Voltage Regulation | 100V/110V/120V/127AC±0.5% or 208V/220V/230V/240VAC±0.5%(AC Mode±10%) | ||||||||||
Frequency | 50HZ/60HZ±0.5HZ Auto(AC Mode±2.5HZ) | ||||||||||
Surge Power | 2700W | ||||||||||
Battery Efficiency | 81% | ||||||||||
AC Efficiency | 93% | ||||||||||
Transfer Time | 8ms default, 4ms optional | ||||||||||
Waveform | Pure Sinewave | ||||||||||
BATTERY | |||||||||||
Battery Voltage | 24VDC | ||||||||||
Floating Charge Voltage | 27.2VDC | ||||||||||
Overcharge Protection | 30.0VDC | ||||||||||
AC Charge Current | 0-20A Adjustable (20A default) | ||||||||||
PROTECTION | |||||||||||
Battery Reversal | Optional | ||||||||||
Output Short Circuit | AC mode:Jump fuse, UPS mode: Shut down | ||||||||||
Overload | Full load 100%, UPS alarm. Overload 120%, UPS shut down output in 10s. Once the load back to normal, UPS recover output. | ||||||||||
High AC Voltage | Turn off AC,turn to UPS mode automatically | ||||||||||
Low DC Voltage | UPS shut down automatically,Once the AC recover, UPS turn on and charge automatically | ||||||||||
Over Temperature | Power Off | ||||||||||
ENVIRONMENT | |||||||||||
Humidity | 15~93%(No condensation) | ||||||||||
Temperature | -10℃ ~ 50℃ | ||||||||||
Altitude | ≤3000m | ||||||||||
Communication | USB, RS232, 485, SNMP (Optional) | ||||||||||
MECHANICAL SPECIFICATIONS | |||||||||||
Dimension, DxWxH (mm) | 483×390×88 [2U] | ||||||||||
Net Weight (Kgs/PC) | 11.30 |