Provides reliable power protection and advanced technology for high power applications.
Prostar GT500K 3 phase uninterruptible power supply ups 500kva meets the unique requirements of medium to large data centers, industry, buildings, and mission-critical environments. This UPS includes ECO Mode, with cost-saving energy efficiency, and SPoT operation mode, which increases on-site test capability without additional load bank.
Uranus Series Low Frequency Online UPS includes 3-phase ins and 3-phase outs from GT6K-GT500K, which can be in parallel with 8 units UPS directly, conveniently and fast. flexible parallel technology could be applied to different loads and systems. According to the needs of customers’ constitute, it could make N+1 or N+X construction, but also according to the different needs of customers with different capacity, it could be in parallel with random 8 units UPS, and all the load will be loaded by all 8 units UPS averagely of the parallel redundant UPS system. Any UPS of the parallel redundant system was failed, the UPS will share its load immediately, to ensure system running normally. During the process of the parallel UPS, it does not set the host and the standby one, but was selected by customers flexibly. The first turned on UPS is automatically set to the host, when the host system failed, the host identity immediately transferred to another UPS, thereby ensuring the supply of electricity for clients during the using process, so it could become a true uninterruptible power supply.
During normal operation, Prostar ups 500kva will provide precise regulated and transient-free power to the critical applications. The mains supply provides power to the rectifier/charger.
The rectifier/charger will provide regulated DC power to support the inverter and simultaneously maintain the battery in a fully chargeed condition.
The inverter will convert the DC power into regulated AC power for the load.
Upon failure of the mains supply, input power for the inverter will automatically be supplied from the directly connected battery. When the mains is restored or the standby generator set supply is ready, input power for the inverter and for recharging the battery will automatically be supplied from the rectifier/charger.
If the input does not return, the UPS 500kva will automatically shut itself down in an orderly manner when the discharge limit of the battery is reached.
Upon the failure of static inverter, the no-break static transfer switch will be activated automatically to isolate the faulty inverter and at the same time maintain a continuous supply to the system load. The automatic transfer mode will also operate in the event of system overloading or if irregular or undesirable output for the load is detected. In this case, the system would automatically return to the original mode of operation if the disturbance is cleared.
If the UPS system needs to be isolated for testing or removed from service for maintenance, the maintenance bypass will transfer the loads from inverter to the mains without interruption and vice versa.
Core system uses the world’s most advanced all-digital DSP control technology, which can effectively guarantee the UPS’ core system accurate, and fast running.
Combined high-reliable and high-efficiency IGBT inverter technology with high-frequency Pulse Width Modulation technology (PWM).
It could reduce noise and power loss, to ensure users can load in a variety of working situations and obtain high-quality voltage output and maximum cost-effectiveness, but also make input efficiency more than 95%.
Reliable and stable, after filtered and regulated, the output sine wave from pure-online double conversion technology, not only has the atmospheric disturbance suppression filter, but also with the standard output isolation transformers, static bypass, maintenance bypass, make this product with higher ability to engage in short circuit current. And it can be applied to the worst working environment.
Perfectly system protection functions: It has AC over-voltage, under-voltage, output over-voltage, under-voltage, output overload, short circuit protection, inverter, rectifier over-temperature protection, voltage under-voltage warning, battery over charging protection and other protections in one to ensure the system to operate stably and reliably.
Durable and reliable design of industrial-type modular structure, combined with full digital DSP control technology core system, make this product not only can be used for N +1 / N + X redundancy and the ability of enlarge the capacity, but also permit different power and different times of the UPS could be in parallel. It greatly reduced the user’s pre-and post-purchasing costs, and increased capacity costs, but also expanded upper spaces of increasing capacity.
The standard equipped with RS232 interface, do contact relays, emergency switching device EPO input interface.
To achieve more than 98% of ultra-high efficiency under ECO economic model, which can effectively bring down the amount of electricity, and effective in accordance with the requirements of energy-saving target of the country.
LCD panel automatic detection function and timely warning in advance, with the boot self-diagnosis function. It could avoid the hidden danger in time due to UPS’ failure, which caused risks. Also it could automatically alarm by setting the battery discharge to standby time is less than a set value.
Humanized panel settings, the users can set system parameters, date, output voltage, battery capacity, alarm function, light-load shutdown, system boot time, MODEM settings, such as orders, also it can be up to 120 abnormal failure information for users to query.
This product has superior environmental adaptability, wide AC input range, greatly reduces the frequency of battery using, and effectively extends the battery life.
Using the pure-online double conversion technology, with the output isolation transformers, static bypass, and maintenance bypass.
Inverter Overload Ability reached 110% / 125% / 150% overloading time can last for 300min/10min/1min.
Bypass Overload Ability reached 150% / 170% / 250% overloading time can last for 60min/10min/1min.
Model | GT500K |
Capacity | 500KVA/400KW |
UPS Efficiency | >95% |
Noise | 48dB~54dB(Distance 1 Meter) |
Dimension(WxDxH mm) | 1630x1026x1902 |
Weight(Kgs) | 2850 |
INPUT | |
Voltage | 3 Phases 4 Wires, 380Vac/400Vac/415Vac ± 25% |
Frequency | 50Hz/60Hz±5% (Automaticly) |
Power Factor | ≥0.95 |
OUTPUT | |
Voltage | 3 Phases 4 Wires, 380Vac/400Vac/415Vac ± 1% |
Frequency | 50Hz/60Hz±0.05%(By Battery) |
Harmonic Distortion | Linear load<3%, Non-linear load<5% |
Imbalance Voltage | Balance load≤1%, Imbalance load≤3% |
Phase Shif Angle | Balance load≤1°, Imbalance load≤2° |
Transient Response | Output at 0~50%~100% ≤5%, response ≤ 10ms |
Overload Capacity | 110%≥300Min, 125%≥10Min, 150%≥1Min |
Crest Factor | 3:1 |
Wave Form | Pure sine wave |
Transfer Time | 0ms |
BATTERY | |
Type | Support VRLA Battery |
D.C. Voltage | 480Vdc |
Max. Charging Current | 0.2AxC10 |
Charging Time(Standard) | 12hours |
SYSTEM | |
Protection | Input over-voltage, under-voltage; output overload, shortcircuit; Inverter over-temperature; Battery under-voltage,over-voltage |
IP Protection | IP20 |
Parallel Mode | N+1,N+X,can be in parallel with differenct power capacity |
Software Interface | Windows9x,2000,NT,ME,XP,Linux,Novell,Macosx,NT4.0 |
Meantime Between Failures | 300,000Hours |
ENVIRONMENT | |
Operating Temperature | 0℃ to 40℃ |
Humidity | 0~95% (non-condensing) |
Altitude | <1000m (with increase of 100m,it will reduce output of 1%) max. 4000m |
Storage Temperature | -15℃ to 50℃ |
MANAGEMENT | |
Communication Interface | RS232/RS485 |
Remote Signaling | Dry contact (battery low,battery discharging,bapass/fault),EPO |
Remote Control | EPO and bypass |
SNMP | Power managemetn from SNMP manager and web browser |
Optional | Dustproof & dampproof, Isolating inverter transformer, lightning surge absorption, static switches, manual maintainence switch |